A 200/1 Current Transformer (CT) is wound with 400 turns on the secondary on a toroidal core. When it carries a current of 180 A on the primary, the ratio is found to be -0.5%. If the number of secondary turns is reduced by 1, the new ratio error (in %) will be?

🎲 Try a Random Question  |  Total Questions in Quiz: 118  |  🧠 Study this quiz with Flashcards
This question is part of a full practice quiz:
Electrical Measurements Practice Test: Extension of Instrument Ranges — practice the complete quiz, review flashcards, or try a random question.

Extension of Instrument Ranges topics include: Shunts and multipliers, instrument transformers and its advantages, current transformers errors and design features, C.T. and P.T. differences, potential transformers error reduction and characteristics, advanced problems on indicating instruments, C.T and P.T. Extending the range of an instrument is a concept that measures higher current or voltage values than the instrument's rating. It's done by adding external resistance or impedance in series or parallel.  Here are some ways to extend the range of instruments: Ammeter: To increase the... Show more