Subcooling = saturation temperature (from high-side pressure) − actual liquid line temperature. It tells you how much the liquid refrigerant has been cooled below its condensing temperature, helping ensure solid liquid to the metering device.
 

Why it matters:
• Proper subcooling supports stable metering device operation (especially TXV systems)
• Low subcooling can mean undercharge or condenser not filling with liquid
• High subcooling can mean overcharge or restriction (context matters)
 

Worked example (calculation):
High-side pressure corresponds to Tsat 110°F. Liquid line temp = 98°F.
Subcooling = 110 − 98 = 12°F.
 

1 of 8 Ready
Subcooling is calculated as:
Condensing saturation temperature − liquid line temperature