NEC-Electrician: Conductor Ampacity Basics - Wire Size vs Current — Flashcards | National Electrical Code (NEC) exam | FatSkills

NEC-Electrician: Conductor Ampacity Basics - Wire Size vs Current — Flashcards

Fast review mode: answers are shown by default so you can skim quickly. Hide them if you want to self-test.

Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. Ampacity depends on conductor size (AWG/kcmil), insulation temperature rating (60°C, 75°C, 90°C), ambient temperature, and number of current-carrying conductors per NEC tables (e.g., Table 310.16).

Worked example:
A #12 AWG copper THHN (90°C) conductor is typically rated 30A in the 90°C column, but if termination is rated 60°C, allowable ampacity is limited to 20A (per 60°C column for #12).
 

1 of 8 Ready
Ampacity primarily refers to:
Maximum continuous current without exceeding temperature rating