By Fatskills Exam Guides Team — the exam nerds behind 28,500+ quizzes and 2.1M practice questions across 500+ global exams.
For Electricians & HVAC Techs
Transformers step voltage up or down to match the needs of equipment (e.g., a 480V-to-120V control transformer for a motor starter, or a 7,200V-to-240V padmount transformer for a house). On the job, you’ll need to: - Size a transformer for a new machine (e.g., a 100A, 208V 3-phase welder). - Calculate primary and secondary currents to pick the right wire, breaker, and overcurrent protection. - Verify kVA ratings to ensure the transformer isn’t overloaded (e.g., a 75 kVA transformer feeding a 60 kVA load + 20 kVA of future expansion).
Real-world scenario: You’re installing a 480V-to-120/240V single-phase transformer for a new machine shop. The shop’s total load is 30 kVA. You need to:1. Confirm the transformer’s kVA rating is sufficient.2. Calculate the primary (480V) and secondary (240V) currents to size the wires and breakers.3. Check if the transformer’s impedance (e.g., 2.5%) affects voltage drop under load.
kVA (Kilovolt-Amperes): The transformer’s power rating (like horsepower for motors). 1 kVA = 1,000 volt-amperes. Example: A 50 kVA transformer can handle 50,000 VA of load.
Single-Phase kVA Formula: kVA = (V × I) ÷ 1,000 V = Voltage (V), I = Current (A). Example: A 240V, 100A load = (240 × 100) ÷ 1,000 = 24 kVA.
Three-Phase kVA Formula: kVA = (V × I × 1.732) ÷ 1,000 1.732 = Square root of 3 (for 3-phase power). Example: A 480V, 50A 3-phase load = (480 × 50 × 1.732) ÷ 1,000 = 41.6 kVA.
Primary Current (I?): Current on the input side of the transformer (higher voltage). Single-phase: I? = (kVA × 1,000) ÷ V? Three-phase: I? = (kVA × 1,000) ÷ (V? × 1.732) Example: A 75 kVA, 480V 3-phase transformer’s primary current = (75 × 1,000) ÷ (480 × 1.732) = 90.3A.
Secondary Current (I?): Current on the output side of the transformer (lower voltage). Single-phase: I? = (kVA × 1,000) ÷ V? Three-phase: I? = (kVA × 1,000) ÷ (V? × 1.732) Example: A 75 kVA, 208V 3-phase transformer’s secondary current = (75 × 1,000) ÷ (208 × 1.732) = 208.3A.
Transformer Impedance (%Z): The transformer’s internal resistance (e.g., 2.5%). Higher %Z = more voltage drop under load. Example: A 5% impedance transformer feeding a 100A load will drop 5V per 100V of secondary voltage (e.g., 120V-114V).
Voltage Drop Due to Impedance: Voltage Drop = (I × %Z × V) ÷ 100 I = Secondary current (A), %Z = Impedance, V = Secondary voltage. Example: A 100A load on a 120V transformer with 2.5% impedance = (100 × 2.5 × 120) ÷ 100 = 3V drop (120V-117V).
Transformer Efficiency: Most transformers are 95–99% efficient. Losses are mostly heat. Example: A 50 kVA transformer with 98% efficiency delivers 49 kVA to the load (1 kVA lost as heat).
Wire Sizing for Transformers:
Secondary side: Size for 125% of continuous loads (NEC 210.19(A)). Example: A 90A primary current requires 90 × 1.25 = 112.5A wire (use 1/0 AWG copper).
Breaker Sizing for Transformers:
Mistake: Forgetting to multiply by 1.732 for 3-phase calculations. Correction: Always use kVA = (V × I × 1.732) ÷ 1,000 for 3-phase. Why? 3-phase power isn’t just 3 × single-phase; the phases are 120° apart, so you need the ?3 factor.
Mistake: Sizing wires for 100% of current (ignoring NEC 125% rule). Correction: Multiply primary current by 1.25 for wire sizing. Why? NEC requires wires to handle 125% of continuous loads to prevent overheating.
Mistake: Using the wrong voltage for primary/secondary calculations. Correction: Primary current uses primary voltage, secondary current uses secondary voltage. Why? Current changes with voltage (Ohm’s Law: I = P/V).
Mistake: Ignoring transformer impedance (%Z) for voltage drop. Correction: Check %Z on the nameplate and calculate voltage drop if the load is near full capacity. Why? A 5% impedance transformer can drop 6V on a 120V circuit, causing equipment issues.
Mistake: Oversizing breakers beyond NEC limits (e.g., 300% of primary current). Correction: Primary breaker-250% of primary current (NEC 450.3(B)). Why? Overcurrent protection must account for transformer inrush current but not exceed safe limits.
Example: If your 480V supply is actually 460V, switch to the -5% tap (480V × 0.95 = 456V) to get closer to 480V on the secondary.
Parallel Transformers:
Warning: Mismatched transformers will circulate current and overheat.
Buck-Boost Transformers:
Example: A 240V motor on a 208V supply can use a buck-boost transformer to add 32V (208V + 32V = 240V).
Dry-Type vs. Oil-Filled:
Why? Secondary current = kVA ÷ (V × 1.732).
You’re installing a 50 kVA, 480V-to-120/240V single-phase transformer. What size breaker is needed on the primary side?
Why? Primary breaker-250% of primary current (104.2A × 2.5 = 260.4A max, but 125A is the largest standard size-260.4A).
A 75 kVA transformer has a 3% impedance. If the secondary voltage is 240V and the load is 200A, what is the voltage drop?
Join 4M+ learners. Unlock unlimited quizzes, wrong-answer tracking, flashcards + reminders, study guides, and 1-on-1 challenges.