By Fatskills Exam Guides Team — the exam nerds behind 28,500+ quizzes and 2.1M practice questions across 500+ global exams.
This is how you figure out how much power a building or machine will actually pull so you can size the wires, breakers, and electrical panel correctly. If you get it wrong, breakers trip constantly, wires overheat, or the inspector red-tags your work. Real-world example: You’re wiring a small machine shop with three 240V motors (5 HP, 3 HP, 1 HP), a 120V welder, and twenty 120V outlets. The NEC says you can’t just add up all the watts—you have to apply demand factors (discounts) to some loads. This guide shows you how to calculate the real load so you can pick the right panel and breakers without wasting money on oversized gear.
Mistake: Adding up all motor loads at 100% and sizing the panel based on that. Correction: Motors have high startup currents—NEC requires 125% of FLC for continuous loads. Why? Motors pull 6x their FLC for a split second when starting, so breakers must handle the extra surge.
Mistake: Forgetting to apply demand factors to lighting and small-appliance loads. Correction: Use 35% for loads over 3,000 VA (NEC 220.42). Why? Not all lights and outlets run at full power at the same time—this prevents oversizing.
Mistake: Using the motor’s nameplate amps instead of NEC Table 430.248. Correction: Always use the FLC from the NEC table, not the motor’s label. Why? Nameplate amps can vary by manufacturer, but the NEC table standardizes calculations.
Mistake: Sizing a breaker for a continuous load at 100% instead of 125%. Correction: For loads running 3+ hours, multiply by 1.25. Why? Breakers heat up over time—125% ensures they don’t trip under sustained load.
Mistake: Mixing 120V and 240V loads without converting to VA first. Correction: Convert everything to VA before adding. Why? You can’t add amps directly if they’re on different voltages.
Field Trick: For small shops, 125A panels are the sweet spot—big enough for most tools but not overkill. If you’re unsure, go 200A for future-proofing.
Code Shortcut: For residential panels, the NEC lets you use 100A service if the total load is-10,000 VA (after demand factors). Most houses fall under this.
Motor Wiring Hack: If a motor’s FLC is ? 16A, you can use #14 AWG wire (but still size the breaker at 125%). Example: A 1 HP, 120V motor (16A FLC)-20A breaker but #14 wire is allowed.
Inspector Red Flags: - No demand factors applied-Instant fail. - Breakers sized at 100% for continuous loads-Must be 125%. - Using nameplate amps instead of NEC tables-Always use the book.
Why? NEC 430.22 requires 125% of FLC for continuous loads.
A house has 2,500 sq. ft. of living space. What’s the general lighting load in VA?
Why? NEC Table 220.12 says 3 VA per sq. ft. for lighting.
You have three 120V small-appliance circuits (kitchen, laundry, bathroom). What’s the total VA after demand factors?
Join 4M+ learners. Unlock unlimited quizzes, wrong-answer tracking, flashcards + reminders, study guides, and 1-on-1 challenges.