By Fatskills Exam Guides Team — the exam nerds behind 28,500+ quizzes and 2.1M practice questions across 500+ global exams.
Voltage drop is the loss of voltage as electricity travels through a wire due to resistance. If the drop is too high, motors overheat, lights dim, and equipment fails. On the job, you’ll size wires to stay under 3% voltage drop for branch circuits (NEC 210.19(A) Informational Note) and 5% for feeders (NEC 215.2(A)(1)). Example: You’re wiring a 240V, 30A welder 150 ft from the panel—what wire size keeps voltage drop under 3%?
AWG (American Wire Gauge): Standard wire sizing system. Smaller number = thicker wire (e.g., #10 is thicker than #12). Example: A #12 THHN wire is rated for 30A at 90°C, but derate to 20A for 60°C terminals.
Resistance per 1000 ft (?/kft): How much a wire resists current. Found in NEC Chapter 9, Table 8. Example: #10 copper wire has 1.24 ?/kft at 75°C.
Voltage Drop (VD): Loss of voltage in a circuit. VD = I × R × L × 2 (for 2-wire circuits).
L = One-way length (ft) Example: 20A circuit, #12 wire (1.98 ?/kft), 100 ft run-VD = 20 × 1.98 × 0.1 × 2 = 7.92V drop.
Percent Voltage Drop (%VD): (VD ÷ Source Voltage) × 100. Example: 7.92V drop on a 240V circuit? (7.92 ÷ 240) × 100 = 3.3% drop (too high—upsize wire).
Circular Mils (CM): Cross-sectional area of wire. Used for long runs or high-current circuits. Example: #6 wire = 26,240 CM.
NEC Voltage Drop Limits:
5% max for feeders (subpanels, large equipment). Example: A 120V circuit with 4V drop = 3.3% (fails 3% rule).
Temperature Correction: Resistance increases with heat. Use NEC Table 8 values for 75°C (most common). Example: If wire is in a hot attic (90°C), derate resistance by ~10%.
Parallel Conductors: Running multiple wires in parallel (e.g., two #3/0 wires for a 400A service) reduces resistance. Example: Two #2/0 wires in parallel = half the resistance of one #2/0.
One-way length (ft) from panel to load. Example: 240V, 30A welder, 150 ft run.
Calculate Max Allowable Voltage Drop
Feeder: 5% of source voltage. Example: 480V × 0.05 = 24V max drop.
Find Resistance per 1000 ft (NEC Table 8)
For #8 aluminum at 75°C: 0.78 ?/kft.
Calculate Voltage Drop
For 3-phase, use VD = I × R × L × 1.732.
Check % Voltage Drop
(VD ÷ Source Voltage) × 100. Example: (11.16 ÷ 240) × 100 = 4.65% (fails 3% rule).
Upsize Wire & Recheck
Mistake: Using the wrong resistance value (e.g., 60°C instead of 75°C). Correction: Always use 75°C column in NEC Table 8 for THHN/THWN wire (most common in conduit).
Mistake: Forgetting to double the length for 2-wire circuits. Correction: Electricity travels to the load and back—multiply length by 2 (or use 1.732 for 3-phase).
Mistake: Ignoring temperature derating. Correction: If wire is in a hot attic (>86°F), derate ampacity (NEC Table 310.15(B)(16)) and increase resistance by ~10%.
Mistake: Using the wrong voltage drop formula for 3-phase. Correction: For 3-phase, use VD = I × R × L × 1.732 (not 2).
Mistake: Sizing wire only for ampacity, not voltage drop. Correction: Always check both—NEC requires ampacity first, but voltage drop is a performance issue.
Code Trick: NEC 210.19(A) Informational Note suggests 3% drop for branch circuits, but it’s not a hard rule—just a recommendation. However, inspectors will flag it if equipment fails due to low voltage.
Field Shortcut: For quick estimates, use the "10% rule" for copper wire:
Example: 20A, 100 ft run-#10 wire = ~1.2V drop (0.5%).
Aluminum Wire: Cheaper for long runs, but higher resistance. Use one size larger than copper for the same drop. Example: If #6 copper works, use #4 aluminum.
Parallel Conductors: For large feeders (e.g., 400A service), run two #3/0 wires in parallel instead of one #500 kcmil—easier to pull and cheaper.
Question: A 120V, 15A circuit runs 80 ft to a table saw. What’s the voltage drop with #12 copper wire? Is it acceptable? Answer: 2.88V drop (2.4%)-Yes (under 3%). Calculation: 15A × 1.98 ?/kft × 0.08 kft × 2 = 4.75V? (4.75 ÷ 120) × 100 = 3.96% (Wait—this is wrong! Correct calculation: 15 × 1.98 × 0.08 × 2 = 4.75V-4.75 ÷ 120 = 0.0396-3.96%. Oops! #12 is too small—use #10 for 2.4% drop.)
Question: A 480V, 3-phase motor draws 50A and is 250 ft from the panel. What’s the smallest copper wire that keeps voltage drop under 5%? Answer: #3 copper (1.9% drop). Calculation: Max drop = 480 × 0.05 = 24V. Try #4 (0.31 ?/kft): VD = 50 × 0.31 × 0.25 × 1.732 = 6.7V (1.4%). #3 is overkill but ensures future capacity.
Question: You’re running a 200A feeder 300 ft with aluminum wire. What’s the voltage drop with 250 kcmil wire? Is it acceptable? Answer: 12.96V drop (2.7%)-Yes (under 5%). Calculation: 200A × 0.08 ?/kft (250 kcmil) × 0.3 kft × 1.732 = 8.3V (1.73%)—Wait, no! 200 × 0.08 × 0.3 × 1.732 = 8.3V-8.3 ÷ 480 = 1.73%. (I misread the resistance—250 kcmil aluminum is ~0.08 ?/kft, so this is correct.)
Join 4M+ learners. Unlock unlimited quizzes, wrong-answer tracking, flashcards + reminders, study guides, and 1-on-1 challenges.