By Fatskills Exam Guides Team — the exam nerds behind 28,500+ quizzes and 2.1M practice questions across 500+ global exams.
Article 430 governs the sizing of motor branch-circuit conductors, overload protection, short-circuit and ground-fault protection, and disconnecting means requirements for motors, controllers, and adjustable-speed drives.
Why It Matters: Motors are among the most complex NEC calculations — they involve four separate protection layers (branch-circuit conductors, overload, short-circuit/ground-fault, and feeder), each with different sizing rules and table references. Exam writers exploit the fact that FLC tables are used for conductors and OCPD sizing while nameplate current is used for overload — candidates who mix these up fail every motor question. In the field, incorrect motor protection causes nuisance tripping, motor burnout, and fire.
FLC (Full-Load Current)
NEC table value used for conductor and OCPD sizing — NOT nameplate.
Nameplate Current
Motor's actual rated current; used ONLY for overload device sizing.
Service Factor (SF)
Multiplier on nameplate indicating safe overload capacity; SF ≥1.15 allows 125% overload trip.
Overload Device
Protects motor from sustained overheating; trips at 115%–125% of nameplate FLC.
Branch-Circuit OCPD
Protects conductors from short-circuit and ground-fault; sized per Table 430.52.
Inverse Time Breaker
Breaker with purposeful trip delay that decreases as current increases.
Dual-Element Fuse
Time-delay fuse allowing motor inrush without nuisance opening; max 175% for single-phase.
LRA (Locked-Rotor Amperes)
Starting inrush current; much higher than FLC — why OCPD must be oversized.
In Sight
Visible and not more than 50 ft away; required for disconnect placement.
Motor-Circuit Switch
HP-rated disconnect switch; must be rated in horsepower, not amperes.
Controller
Device to start/stop a motor; HP rating must be ≥ motor HP rating.
Adjustable-Speed Drive (ASD)
Variable frequency drive (VFD); output conductors subject to waveform stress.
Key FLC Values from NEC Tables 430.247–430.250 (Memorize These)
Single Phase 115V
Item 1
Hp: 1
Fla: 16A
Single Phase 230V
Hp: 1.5
Fla: 10A
Item 2
Hp: 2
Fla: 12A
Three Phase 208V
Fla: 7.5A
Hp: 7.5
Fla: 24.2A
Three Phase 230V
Hp: 10
Fla: 28A
Three Phase 460V
Hp: 15
Fla: 21A
Hp: 25
Fla: 34A
Item 3
Hp: 50
Fla: 65A
Single Motor Branch Circuit
Given: 10 hp, 3-phase, 460V motor. Service factor = 1.15. Using dual-element fuse and copper conductors (60°C).
Fla: From Table 430.250: 10 hp, 460V, 3-phase → FLC = 14A
Steps
Summary Table
Conductors: 12 AWG Cu (min 17.5A ampacity → 20A rated)
Overload Trip: ≤17A (125% × nameplate)
Dual Element Fuse: 25A (175% × 14A FLC, rounded up)
Inverse Time Breaker Alternative: 35A (250% × 14A = 35A)
Disconnect: HP-rated switch ≥10 hp, in sight from controller and motor
Multiple Motor Feeder
Given: Three motors on one feeder: Motor 1 = 15 hp, 460V, 3-phase (highest rated). Motor 2 = 10 hp, 460V, 3-phase. Motor 3 = 5 hp, 460V, 3-phase. Using inverse time breaker.
Fla Values
Motor 1 15Hp 460V: 21A (Table 430.250)
Motor 2 10Hp 460V: 14A (Table 430.250)
Motor 3 5Hp 460V: 7.6A (Table 430.250)
Feeder Conductor: 8 AWG Cu (min 47.85A → 50A rated)
Feeder Ocpd: 70A inverse time breaker
Motor 1 Branch Ocpd: 50A inverse time breaker
Motor 2 Branch Ocpd: 35A inverse time breaker
Motor 3 Branch Ocpd: 20A inverse time breaker
Max Branch-Circuit OCPD as % of FLC (Table 430.52(C)(1))
Note: Single-phase values shown. Three-phase values are the same percentages.
Next Size Up Rule: If calculated OCPD size doesn't match a standard rating AND the motor won't start reliably, the next higher standard rating is permitted (430.52(C)(1)(a)).
Rows
Device Type: Dual-element (time-delay) fuse
Max Percent Of Flc: 175%
Device Type: Non-time-delay fuse
Max Percent Of Flc: 300%
Device Type: Inverse time (standard) circuit breaker
Max Percent Of Flc: 250%
Item 4
Device Type: Instantaneous trip breaker (ITB)
Max Percent Of Flc: 800%
Overload Device Trip Thresholds (430.32) — Based on NAMEPLATE Current
SF ≥ 1.15 OR temp rise ≤ 40°C
Condition: SF ≥ 1.15 OR temp rise ≤ 40°C
Max Trip Percent: 125% of nameplate FLC
All other motors
Condition: All other motors
Max Trip Percent: 115% of nameplate FLC
Motors 1 hp or less, non-automatically started
Condition: Motors 1 hp or less, non-automatically started
Max Trip Percent: No separate overload required
Motor Control Circuit OCPD — 430.72(B)(2)
Example: 14 AWG control conductors, extending beyond enclosure: 14 AWG @ 60°C = 15A. Max OCPD = 15A × 300% = 45A.
Conductors DO NOT extend beyond enclosure (Column B, Table 310.16)
Condition: Conductors DO NOT extend beyond enclosure (Column B, Table 310.16)
Max Ocpd: 100% of Table 310.16 ampacity for 60°C
Conductors EXTEND beyond enclosure (Column C, Table 310.16)
Condition: Conductors EXTEND beyond enclosure (Column C, Table 310.16)
Max Ocpd: 300% of Table 310.16 ampacity for 60°C
Question: A 3-phase, 460V, 15 hp motor has a nameplate current of 20A and SF = 1.15. What is the maximum overload trip setting?
Correct Answer: 20A × 125% = 25A. Because SF ≥ 1.15, the overload device may be set up to 125% of the motor's nameplate current per NEC 430.32(A)(1). The FLC table value (21A) is NOT used for overload sizing.
Question: What is the maximum dual-element time-delay fuse size for a single-phase, 230V, 1.5 hp motor?
Correct Answer: From Table 430.248: FLC for 1.5 hp, 230V single-phase = 10A. Table 430.52 allows dual-element fuse at max 175% of FLC: 10A × 175% = 17.5A → next standard fuse size = 20A. (If 17.5A is a standard size it would be used; otherwise next up = 20A.)
Question: Three motors share a feeder: 25 hp (34A), 10 hp (14A), and 5 hp (7.6A), all 460V 3-phase. What is the minimum feeder conductor ampacity?
Correct Answer: Per 430.24: 125% of highest motor + 100% of others. (34A × 1.25) + 14A + 7.6A = 42.5 + 14 + 7.6 = 64.1A minimum ampacity. Select conductor with ≥64.1A ampacity from Table 310.16 — 4 AWG copper (70A).
Style: 5-mark
Question: Describe the four protective elements required for a single motor branch circuit and state the NEC section and sizing basis for each.
Model Answer: A complete motor branch circuit requires four separate protection layers.
(1) Branch-circuit conductors (430.22): sized at minimum 125% of the motor FLC from NEC Tables 430.247–430.250 — not nameplate. (2) Overload protection (430.32): a separate device responsive to motor current, set to trip at no more than 125% of nameplate current if the motor has SF ≥1.15 or temperature rise ≤40°C; otherwise 115% of nameplate. (3) Short-circuit and ground-fault protection (430.52): sized per Table 430.52 using FLC table values — dual-element fuse max 175%, inverse time breaker max 250%. If the calculated size doesn't correspond to a standard rating and the motor won't start, the next higher standard rating is permitted. (4) Disconnecting means (430.102, 430.109): an HP-rated motor-circuit switch or listed device, located in sight from the controller and separately in sight from the motor and driven machinery. Each layer has a distinct sizing basis — mixing nameplate with table values is the most common exam error.
Join 4M+ learners. Unlock unlimited quizzes, wrong-answer tracking, flashcards + reminders, study guides, and 1-on-1 challenges.