By Fatskills Exam Guides Team — the exam nerds behind 28,500+ quizzes and 2.1M practice questions across 500+ global exams.
Article 310 governs conductor ampacity — the maximum current a conductor can carry continuously without exceeding its temperature rating — with Table 310.16 as the primary sizing reference for conductors in raceways or cables.
Why It Matters: Undersized conductors overheat, degrade insulation, and cause fires. Oversized conductors waste material and may not fit terminations. Table 310.16 is one of the highest-frequency exam references — candidates who misread temperature columns, forget the 75°C terminal rule, or skip correction factors lose easy points. Field electricians use this table daily for every circuit they size.
Ampacity
Maximum continuous current a conductor can carry without exceeding its temperature rating.
Table 310.16
Ampacity table for ≤3 conductors in raceway/cable; 30°C ambient; up to 2,000V.
Table 310.17
Ampacity table for single conductors in free air; 30°C ambient; higher values than 310.16.
Temperature Correction Factor
Multiplier from Table 310.15(B)(1)(1) when ambient exceeds 30°C; always <1 above 30°C.
Adjustment Factor
Derating multiplier when >3 current-carrying conductors share a raceway (bundling).
75°C Terminal Rule
Size conductor using 75°C column when equipment terminals are rated 75°C, even if insulation is 90°C.
AWG
American Wire Gauge; inverse scale — higher number = smaller wire; 4/0 > 1 > 10 > 14.
kcmil
Thousands of circular mils; used for conductors larger than 4/0 AWG (e.g., 250 kcmil, 350 kcmil).
Circular Mil
Area of a circle with 1 mil (0.001 inch) diameter; unit for measuring conductor cross-section.
TW
60°C thermoplastic insulation; lowest ampacity column; dry/wet locations.
THW / THWN
75°C thermoplastic; dry/wet locations; most common conduit wiring.
THHN
90°C thermoplastic; dry only; highest ampacity column — but limited to 75°C at most terminals.
THWN-2
90°C thermoplastic; dry and wet; W = wet rated, 2 = 90°C in both conditions.
RHW
75°C thermoset rubber insulation; dry/wet; thermoset ≠ thermoplastic.
Compact Stranding
Used with aluminum conductors to reduce overall diameter; easier conduit fill.
NM Cable (Romex)
Nonmetallic sheathed cable for dry residential use; 90°C conductors derated to 60°C for ampacity.
Type UF Cable
Underground feeder; suitable for direct burial; NOT the same as NM (Romex).
Type USE Cable
Underground service entrance cable; direct burial permitted; 75°C rated.
Type AC Cable (BX)
Armored cable with fire-retardant paper wraps on individual conductors and a bonding strip.
Type MC Cable
Metal-clad cable; metal armor serves as EGC; no fire-retardant conductor wraps; 18 AWG to 2,000 kcmil.
Type NMC
Nonmetallic sheathed cable for dry/damp/corrosive locations; NOT suitable for direct burial or concrete.
Formula: Corrected Ampacity = Table Ampacity × Correction Factor
Key Rule: As ambient temperature INCREASES above 30°C, ampacity DECREASES. Correction factors above 30°C are always less than 1.00. Correction factors below 30°C are greater than 1.00.
Example 1
Conductor: 1 AWG THW copper
Table Ampacity: 130A (75°C column)
Ambient: 55°C
Correction Factor: 0.75
Calculation: 130 × 0.75 = 97.5 → 97A
Example 2
Ambient: 110°F (≈43°C)
Correction Factor: 0.82
Calculation: 130 × 0.82 = 106.6 → 107A
Note: Only current-carrying conductors count toward the total. Grounding conductors and neutrals carrying only unbalanced current do NOT count.
4 To 6 Conductors: 0.80 (80%)
7 To 9 Conductors: 0.70 (70%)
10 To 20 Conductors: 0.50 (50%)
Note: Hard limits regardless of Table 310.16 values. Example: 10 AWG THHN shows 40A in Table 310.16 (90°C column) — but 240.4(D) caps OCPD at 30A.
14 Awg Copper: Maximum 15A OCPD
12 Awg Copper: Maximum 20A OCPD
10 Awg Copper: Maximum 30A OCPD
Note: Selected ampacity values at 30°C ambient for common conductor sizes.
Copper 60C Tw
14 Awg: 15A
12 Awg: 20A
10 Awg: 30A
8 Awg: 40A
6 Awg: 55A
4 Awg: 70A
2 Awg: 95A
1 Awg: 110A
1/0 Awg: 125A
2/0 Awg: 145A
3/0 Awg: 165A
4/0 Awg: 195A
Copper 75C Thw Thwn Rhw
14 Awg: 20A
12 Awg: 25A
10 Awg: 35A
8 Awg: 50A
6 Awg: 65A
4 Awg: 85A
2 Awg: 115A
1 Awg: 130A
1/0 Awg: 150A
2/0 Awg: 175A
3/0 Awg: 200A
4/0 Awg: 230A
250 Kcmil: 255A
350 Kcmil: 310A
Copper 90C Thhn Thwn2
14 Awg: 25A
12 Awg: 30A
10 Awg: 40A
8 Awg: 55A
6 Awg: 75A
4 Awg: 95A
2 Awg: 130A
1 Awg: 150A
1/0 Awg: 170A
2/0 Awg: 195A
3/0 Awg: 225A
4/0 Awg: 260A
250 Kcmil: 290A
350 Kcmil: 350A
Aluminum 75C Thw Thwn Rhw
6 Awg: 50A
4 Awg: 65A
2 Awg: 90A
1 Awg: 100A
1/0 Awg: 120A
2/0 Awg: 135A
3/0 Awg: 155A
4/0 Awg: 180A
250 Kcmil: 205A
350 Kcmil: 250A
Tw: 60°C; thermoplastic; dry/wet; lowest ampacity.
Thw: 75°C; thermoplastic; dry/wet; most common in conduit.
Thwn: 75°C; thermoplastic; dry/wet.
Thhn: 90°C; thermoplastic; dry only; size at 75°C column for most terminals.
Thwn 2: 90°C; thermoplastic; dry and wet; use 90°C column if terminals allow.
Rhw: 75°C; thermoset (rubber); dry/wet.
Rhh: 90°C; thermoset; dry only.
Xhhw: 90°C dry / 75°C wet; cross-linked polyethylene.
Xhhw 2: 90°C dry and wet; highest rating for wet locations.
Nm Romex: 90°C conductors — must use 60°C column for ampacity (NEC 334.80).
W Suffix: Conductor marked W is rated for wet/outdoor locations.
R Prefix: R = rubber (thermoset) insulation base material.
Nm Romex: Dry residential only; 90°C conductors derated to 60°C column.
Nmc: Dry, damp, corrosive — NOT direct burial, NOT embedding in concrete.
Ac Bx: Armored; fire-retardant paper wraps on conductors; bonding strip inside.
Mc: Metal-clad; armor = EGC; no fire-retardant wraps; 18 AWG to 2,000 kcmil.
Use: Underground service entrance; direct burial OK; 75°C.
Uf: Underground feeder; direct burial OK; 60°C; NOT called Romex.
Mv: Medium voltage (>2,000V); wet, dry, and direct burial all permitted.
Key Ac Vs Mc: AC cable has fire-retardant paper wraps on individual conductors; MC does not.
Scenario: 3-phase 480V circuit, 98A calculated load. Three copper conductors in RMC. Terminals rated 75°C.
Thhn: 90°C insulation but terminal = 75°C → use 75°C column. 3 AWG Cu @ 75°C = 100A ≥ 98A. Answer: 3 AWG.
Thw: 75°C column directly. 3 AWG = 100A ≥ 98A. Answer: 3 AWG.
Tw: 60°C column. 3 AWG = 85A (not enough). 2 AWG = 95A (not enough). 1 AWG = 110A ≥ 98A. Answer: 1 AWG.
Lesson: THHN and THW both land on 3 AWG because the 75°C terminal rule equalizes them. TW requires one size larger because its 60°C column values are lower.
Scenario: Replace 1 AWG TW aluminum with minimum THHN copper of equal ampacity.
Step 1: 1 AWG TW aluminum @ 60°C column = 75A.
Step 2: THHN copper but terminals are 75°C → use 75°C Cu column. Find ≥75A: 6 AWG = 65A (not enough); 4 AWG = 85A ≥ 75A.
Answer: 4 AWG THHN copper.
Lesson: Replacing aluminum with copper does not always mean going up in AWG. The 75°C terminal rule governs which column to use even for THHN.
Scenario: 4 AWG SE cable with 90°C aluminum conductors, terminated to 75°C equipment.
Step: 90°C insulation, but terminal is 75°C → use 75°C Al column. 4 AWG Al @ 75°C = 65A.
Answer: 65A per conductor.
Lesson: SE and USE cables often have 90°C insulation but are limited to 75°C ampacity at standard equipment terminals.
Question: A 3-phase 240V circuit has a calculated load of 196A. Three RHW copper conductors in EMT. Terminals rated 75°C. What conductor size is required?
Correct Answer: 3/0 AWG copper. RHW is 75°C; terminals are 75°C → use 75°C Cu column. 3/0 AWG = 200A ≥ 196A. 2/0 AWG = 175A is insufficient.
Question: What does Table 310.16 list for 10 AWG THHN copper, and what does 240.4(D) limit the OCPD to?
Correct Answer: Table 310.16 lists 10 AWG THHN at 40A (90°C column). NEC 240.4(D)(8) limits the OCPD to 30A maximum for 10 AWG copper regardless of insulation type.
Question: A conductor's ampacity must be reduced when ambient temperature rises above what baseline?
Correct Answer: 30°C (86°F). This is the baseline ambient temperature for Table 310.16 and 310.17. Any ambient above 30°C requires applying a correction factor less than 1.00 to reduce the table ampacity.
Style: 5-mark
Question: A calculated load is 173A. Identify the minimum size copper conductor permitted considering all insulation types. Explain the 75°C terminal rule and its effect on your answer.
Model Answer: Step 1 — Check Table 310.16 across all temperature columns for copper. At 60°C (TW): 3/0 AWG = 165A (insufficient); 4/0 AWG = 195A ✓. At 75°C (THW/THWN/RHW): 2/0 AWG = 175A ✓. At 90°C (THHN): 2/0 AWG = 195A ✓. Step 2 — The 75°C terminal rule (NEC 110.14(C)): most standard equipment terminals are rated 75°C. Even if the conductor insulation is 90°C (e.g., THHN), ampacity must be based on the 75°C column unless the equipment is specifically listed and marked for 90°C terminations. Step 3 — Result: The minimum conductor is 2/0 AWG copper (achievable with THW, THWN, RHW, THHN, or THWN-2 all sized using the 75°C column). Using TW (60°C only) requires 4/0 AWG — two sizes larger. The 75°C terminal rule is the reason THHN, despite being rated 90°C, provides the same minimum conductor size as THW in this scenario.
Join 4M+ learners. Unlock unlimited quizzes, wrong-answer tracking, flashcards + reminders, study guides, and 1-on-1 challenges.