By Fatskills Exam Guides Team — the exam nerds behind 28,500+ quizzes and 2.1M practice questions across 500+ global exams.
Table 310.16 gives base ampacity for insulated conductors in a raceway or cable at 30°C ambient with no more than 3 current-carrying conductors — any deviation in temperature or conductor count requires correction and adjustment factors before a conductor size can be selected.
Why It Matters: Every conductor sizing question on the exam starts at Table 310.16 but rarely ends there — ambient temperature above 30°C and more than 3 conductors in a raceway both derate ampacity. Candidates who skip derating pass the table lookup but fail the final answer. In the field, undersized conductors overheat insulation, cause fires, and fail inspection.
Ampacity
Maximum continuous current a conductor can carry without exceeding its temperature rating.
Base Ampacity
Table 310.16 value before any correction or adjustment is applied.
Temperature Correction Factor
Multiplier from Table 310.15(B)(1) applied when ambient temp ≠ 30°C.
Adjustment Factor
Multiplier from Table 310.15(C)(1) applied when >3 current-carrying conductors share a raceway.
Current-Carrying Conductor (CCC)
Any conductor that carries load current; EGC and neutral (unbalanced only) excluded.
60°C Column
Governs conductor sizing at most standard terminations (breakers, lugs) unless listed for higher temp.
75°C Column
Permitted for terminations listed for 75°C; most commercial/industrial lugs qualify.
90°C Column
Used ONLY to calculate correction/adjustment — not for final ampacity unless terminations are 90°C rated.
Continuous Load
Load expected to run ≥3 hours; conductor must be sized at 125% before table lookup.
Parallel Conductors
Two or more conductors per phase, same size/type/length, connected at both ends; each must be individually rated.
Voltage Drop
Voltage lost to conductor resistance over distance; VD = I × R (or 2 × K × I × L ÷ CM for single-phase).
Circular Mils (CM)
Unit of conductor cross-sectional area used in voltage drop calculations.
Table 310.16 Base Ampacity — Copper THHN/THWN-2 (Most Common Exam Values)
Note: Values shown for 60°C and 75°C columns. 90°C column used only for derating math, not final sizing at standard terminations.
Rows
Item 1
Awg Kcmil: 14 AWG
Col 60C: 15A
Col 75C: 20A
Col 90C: 25A
Item 2
Awg Kcmil: 12 AWG
Col 60C: 20A
Col 75C: 25A
Col 90C: 30A
Item 3
Awg Kcmil: 10 AWG
Col 60C: 30A
Col 75C: 35A
Col 90C: 40A
Item 4
Awg Kcmil: 8 AWG
Col 60C: 40A
Col 75C: 50A
Col 90C: 55A
Item 5
Awg Kcmil: 6 AWG
Col 60C: 55A
Col 75C: 65A
Col 90C: 75A
Item 6
Awg Kcmil: 4 AWG
Col 60C: 70A
Col 75C: 85A
Col 90C: 95A
Item 7
Awg Kcmil: 3 AWG
Col 60C: 85A
Col 75C: 100A
Col 90C: 110A
Item 8
Awg Kcmil: 2 AWG
Col 60C: 95A
Col 75C: 115A
Col 90C: 130A
Item 9
Awg Kcmil: 1 AWG
Col 60C: 110A
Col 75C: 130A
Col 90C: 145A
Item 10
Awg Kcmil: 1/0 AWG
Col 60C: 125A
Col 75C: 150A
Col 90C: 170A
Item 11
Awg Kcmil: 2/0 AWG
Col 60C: 145A
Col 75C: 175A
Col 90C: 195A
Item 12
Awg Kcmil: 3/0 AWG
Col 60C: 165A
Col 75C: 200A
Col 90C: 225A
Item 13
Awg Kcmil: 4/0 AWG
Col 60C: 195A
Col 75C: 230A
Col 90C: 260A
Item 14
Awg Kcmil: 250 kcmil
Col 60C: 215A
Col 75C: 255A
Col 90C: 290A
Item 15
Awg Kcmil: 350 kcmil
Col 60C: 260A
Col 75C: 310A
Col 90C: 350A
Item 16
Awg Kcmil: 500 kcmil
Col 60C: 320A
Col 75C: 380A
Col 90C: 430A
Table 310.15(B)(1) — Temperature Correction Factors (90°C Rated Conductors, THHN)
Note: Multiply base 90°C ampacity by this factor, then compare to 60°C or 75°C termination limit.
Ambient C: 10°C or less
Factor 90C: 1.15
Ambient C: 11–15°C
Factor 90C: 1.12
Ambient C: 16–20°C
Factor 90C: 1.08
Ambient C: 21–25°C
Factor 90C: 1.04
Ambient C: 26–30°C
Factor 90C: 1.00
Ambient C: 31–35°C
Factor 90C: 0.96
Ambient C: 36–40°C
Factor 90C: 0.91
Ambient C: 41–45°C
Factor 90C: 0.87
Ambient C: 46–50°C
Factor 90C: 0.82
Ambient C: 51–55°C
Factor 90C: 0.76
Ambient C: 56–60°C
Factor 90C: 0.71
Ambient C: 61–70°C
Factor 90C: 0.58
Ambient C: 71–80°C
Factor 90C: 0.41
Table 310.15(C)(1) — Adjustment Factors for More Than 3 CCCs in Raceway or Cable
Num Ccc: 4–6
Adjustment Factor: 0.80 (80%)
Num Ccc: 7–9
Adjustment Factor: 0.70 (70%)
Num Ccc: 10–20
Adjustment Factor: 0.50 (50%)
Num Ccc: 21–30
Adjustment Factor: 0.45 (45%)
Num Ccc: 31–40
Adjustment Factor: 0.40 (40%)
Num Ccc: 41+
Adjustment Factor: 0.35 (35%)
Copper vs. Aluminum — Key Exam Distinctions
Property: Conductivity
Copper: Higher — smaller wire for same ampacity
Aluminum: Lower — 2 AWG sizes larger for same ampacity (general rule)
Property: Weight
Copper: Heavier
Aluminum: Lighter — preferred for large feeders and services
Property: Termination requirement
Copper: Standard lugs
Aluminum: Anti-oxidant compound required; AL-rated lugs only
Property: Minimum size permitted
Copper: 14 AWG (branch circuits)
Aluminum: 12 AWG (branch circuits per 310.3)
Property: Common application
Copper: Branch circuits, motor circuits
Aluminum: Services, large feeders, utility runs
Property: Example equivalence
Copper: 2 AWG Cu = 115A (75°C)
Aluminum: 1/0 AWG Al = 120A (75°C) — roughly 2 sizes larger
Table 310 16 Aluminum Key Values
Awg Kcmil: 12 AWG Al
Awg Kcmil: 10 AWG Al
Col 60C: 25A
Col 75C: 30A
Awg Kcmil: 8 AWG Al
Col 75C: 40A
Awg Kcmil: 6 AWG Al
Awg Kcmil: 4 AWG Al
Awg Kcmil: 2 AWG Al
Col 60C: 75A
Col 75C: 90A
Awg Kcmil: 1/0 AWG Al
Col 60C: 100A
Col 75C: 120A
Awg Kcmil: 2/0 AWG Al
Col 60C: 115A
Col 75C: 135A
Awg Kcmil: 3/0 AWG Al
Col 60C: 130A
Col 75C: 155A
Awg Kcmil: 4/0 AWG Al
Col 60C: 150A
Col 75C: 180A
Awg Kcmil: 250 kcmil Al
Col 60C: 170A
Col 75C: 205A
Awg Kcmil: 350 kcmil Al
Col 60C: 210A
Col 75C: 250A
Scenario A — Single Conductor with Temperature + Fill Derating
Given: A circuit carries 60A continuous load. Conductors are copper THHN (90°C rated) in a conduit with 6 total current-carrying conductors. Ambient temperature is 45°C. Equipment terminations are rated 75°C.
Steps
Summary
Required Ampacity After Derate: 107.8A
Conductor Selected: 3 AWG Cu THHN
90C Ampacity: 110A
75C Termination Check: 100A ≥ 75A — passes
Scenario B — Parallel Conductors
Given: A 400A feeder is required. Copper THHN conductors, 75°C terminations, 30°C ambient, 3 conductors per raceway (standard conditions — no derating). Two parallel sets will be used.
Rules For Parallel Conductors
Total Load: 400A
Parallel Sets: 2
Load Per Set: 200A
Conductor Per Set: 3/0 AWG Cu THHN (200A @ 75°C)
Minimum Size Rule: 1/0 AWG or larger — 3/0 AWG complies
Voltage Drop Calculation — Exam Formula
Nec Recommendation: NEC recommends (not mandates): ≤3% VD on any branch circuit; ≤5% combined feeder + branch circuit total.
Formulas
Single Phase Vd: VD = (2 × K × I × L) ÷ CM
Three Phase Vd: VD = (1.732 × K × I × L) ÷ CM
Percent Vd: % VD = (VD ÷ Source Voltage) × 100
Variables
K: Resistivity constant: 12.9 for copper, 21.2 for aluminum (ohm-circular mil per foot)
I: Load current in amperes
L: One-way length of circuit in feet
Cm: Circular mils of conductor (from conductor tables)
Common Cm Values
Awg: 14 AWG
Cm: 4,110
Awg: 12 AWG
Cm: 6,530
Awg: 10 AWG
Cm: 10,380
Awg: 8 AWG
Cm: 16,510
Awg: 6 AWG
Cm: 26,240
Awg: 4 AWG
Cm: 41,740
Awg: 2 AWG
Cm: 66,360
Awg: 1/0 AWG
Cm: 105,600
Awg: 2/0 AWG
Cm: 133,100
Awg: 3/0 AWG
Cm: 167,800
Worked Example
Scenario: 120V single-phase branch circuit, 16A load, 80 ft one-way run, 12 AWG copper. Is voltage drop within 3%?
Answer: 12 AWG fails VD check (4.2%); 10 AWG passes (2.65%).
Question: A 12 AWG copper THHN conductor is in a conduit with 8 current-carrying conductors at 40°C ambient. What is its derated ampacity? (Use 90°C column for calculation; cap at 60°C termination limit.)
Correct Answer: 90°C base for 12 AWG Cu = 30A. Temp correction at 40°C = 0.91. Adjustment for 7–9 CCCs = 0.70. Derated ampacity = 30A × 0.91 × 0.70 = 19.1A. However, 60°C column for 12 AWG = 20A. The derated value (19.1A) is LESS than the 60°C cap (20A), so derated ampacity = 19.1A governs. Always use the lower of the two.
Question: A feeder must carry 300A. No derating applies. What is the smallest single copper conductor permitted, and what is the smallest configuration using parallel conductors?
Correct Answer: Single conductor: 350 kcmil Cu @ 75°C = 310A → 350 kcmil is the smallest single conductor ≥300A. Parallel conductors: 300A ÷ 2 sets = 150A per set. 1/0 AWG Cu @ 75°C = 150A → two sets of 1/0 AWG Cu (each set ≥1/0 AWG minimum for parallel — complies). Parallel option uses smaller individual conductors but requires two conduits.
Question: A 240V single-phase circuit carries 30A over a 120 ft one-way run using 10 AWG copper. What is the voltage drop percentage?
Correct Answer: VD = (2 × 12.9 × 30 × 120) ÷ 10,380 = 92,880 ÷ 10,380 = 8.95V. % VD = (8.95 ÷ 240) × 100 = 3.7%. Exceeds the NEC 3% recommendation for branch circuits — upsize to 8 AWG (CM = 16,510): VD = 92,880 ÷ 16,510 = 5.63V → 2.3% → within 3%.
Style: 5-mark
Question: A 50A continuous load is served by copper THHN conductors in a conduit containing 9 current-carrying conductors. Ambient temperature is 50°C. Equipment terminations are rated 75°C. Select the minimum conductor size and show all steps.
Model Answer: Step 1 — Continuous load adjustment: 50A × 125% = 62.5A minimum required ampacity before derating. Step 2 — Temperature correction (Table 310.15(B)(1)): Ambient = 50°C, THHN = 90°C rated → factor = 0.82. Step 3 — Adjustment factor (Table 310.15(C)(1)): 9 CCCs → factor = 0.70. Step 4 — Combined factor: 0.82 × 0.70 = 0.574. Step 5 — Required 90°C base ampacity: 62.5A ÷ 0.574 = 108.9A. Step 6 — Select from 90°C column: 3 AWG Cu = 110A → 110A > 108.9A → fits. Step 7 — Verify termination cap (75°C): 3 AWG Cu @ 75°C = 100A. Check: 100A ≥ 62.5A required → passes. Answer: 3 AWG copper THHN minimum.
Join 4M+ learners. Unlock unlimited quizzes, wrong-answer tracking, flashcards + reminders, study guides, and 1-on-1 challenges.